Kitchen Fire Suppression System (Triple Zone GP 10)
Certified with the CE
Temperature adjustment according to kitchen environment
Equipped with built-in backup battery
Features
Detect and extinguish fires in up to three zones.
May be used in conjunction with other devices with additional external sirens, manual switches, and contact signals.
Temperature adjustment (scope of configuration between 20°C ~ 250°C) depending on commercial kitchen environment.
1st and 2nd stage warning system based on temperature sensing.
- During the 1st stage warning, the gas valve, damper, and turned off the electricity
- During the 2nd stage warning, the automatic fire suppression system is activated simultaneously
The control panel enables easy maintenance and repairs with its self-diagnostic features
Use of the fire extinguishing agent that is optimized and enhanced for class K fires.
When the fire extinguishing agent is released, it protects the environment by not leaving behind a residue.
Components of Kitchen Fire Suppression Systems
No.
Description
Number that can be installed
1
Temperature sensor
8
2
Fire Extinguisher
3
3
Nozzle
9
4
Gas detector
3
5
Gas shutoff device
1
6
Damper
1
7
Magnetic Contactor
1
8
Siren
1
9
Manual Switch
1
10
Control Panel
1
Specification
Control panel: GP 10
Division
Spec.
Working Voltage
85~264V AC
Frequency Range
50~63Hz
Power Consumption
17W(reserve), 27W(normal)
Backup Battery
Ni-Cd Battery/DC 24V 1.3Ah
Display
8" TFT LCD Color
Operating Temperature
-20°C~40°C
Size(mm)
333(W) x 260(H) x 68(D)
Weight(kg)
4.1
Temperature Sensor: TS 033
Division
Specification
Type
Temperature sensor type(Thermistor type)
Level(1st)
Operation temperature(Default)
95°C
Operating Range
50°C~250°C
Level(2nd)
Operation temperature(Default)
140°C
Operating Range
50°C~250°C
Fire Extinguisher: FE 036
Division
Spec.
Chemical formula
K2CO3
Capacity / Charge
5.1L / 3.6L
Material / Thickness
STS 304 / 1.2t
Charging Pressure
9.8kg/cm2
Operating Temperature
-20°C~40°C
Ejection Time
Within 60 seconds
Size(mm)
Ø140 x 455
Charged Weight(kg)
7.12
Discharge Nozzle: DN 045(065)
Division
Spec.
Ejection Angle
45°, 65°
Available Height of Installation
1m~1.3m
Spraying Area
600mm~700mm
Material
Copper Allpy / Chrome - coated
Size(mm)
Ø21x74 / Ø16x45
Weight(g)
120/60
Gas Detector: GD 100(101)
Division
Spec.
Working Voltage
12V DC
Sensing
Catalytic Combustion Type
Detectable Gases
LPG, LNG
Sensing Density
Less than 1/4 of the Lower-Explosive Limit(LEL)
LPG(0.45%), LNG(1.25%)
Working Current
110nA
Operating Temperature
-20°C~40°C
Size(mm)
70(W) x 96(H) x 35(D)
Weight(g)
80
Gas Shutoff Device: SD 020(032)
Division
Spec.
Working Voltage
12V DC
24V DC
Pipe Size
15,20,25(mm)
1/2",3/4",1"
32,40(mm)
1 1/4", 1 1/2"
Shut-off Speed
Within 12 seconds
Within 20 seconds
Shut-off Torque
More than 5.9(N,m)
More than 98(N,m)
Durability
More than 6,000times
More than 3,000times
Operating Temperature
-20°C~40°C
Size(mm)
111(W) x 165(H) x 75(D)
126(W) x 180(H) x 300(D)
Weight(g)
0.68
2.7
*You can take a pick of a gas shut-off device for 15A(1/2B), 20A(3/4B), 25A(1B), 32A(1 1/4B) or 40A(1 1/2B)
Damper: FD 024
Division
Spec.
Working Voltage
24V DC
Power Consumption
80mA(minimum)±10%
500mA(maximum)±10%
Shut-off Speed
Within 25 seconds
Working Angle
0~90° ±5°
Operating Wind Speed
Less than 15m/sec
Size(mm)
85(W) x 160(H) x 73(D)
Weight(kg)
0.78
Weight(g)
*For option
Magnetic Contactor: MC 018
Division
Spec.
Frame Size
22AF
Number of poles
3 pole
Rated current
18A
Rated insulation voltage
690V
*For option
Siren: FS 024
Division
Spec.
Working Voltage
24V DC
Alarm Sound
90~100dB
Flash Intensity
About 1.2WS
Flash Period
About 1.5S
Size(mm)
130(W) x 125(H) x 48(D)
Weight(g)
140
*For option
Manual Switch: MS 100
Division
Spec.
Driving Method
Contact point method
Operating Temperature
-20°C~40°C
Size(mm)
88(W) x 52(H) x 88(D)
Weight(g)
170
*For option
*The specifications or form of the product pictured above many change.